產(chǎn)品詳情
SUBSTATION GROUNDING SET AND GROUND LIFTING TOOL
? The below listed tools enable operating personnel the capability of grounding de-energized
substations safely and easily with use of the ground lifting tool.
? Two ranges of ground clamps, both have bolted type pressure terminals.
? Ground clamps are mounted on an 8’ fiberglass pole. The bottom end of the clamp mounted
pole has a fiberglass male splice to allow extension sections to be added to meet the required
height for applying the ground set.
? The ground lifting tool has a universal end and is supplied with a large opening “C” hook that
is coated for protection. It comes complete with handline block, adjustable block clamp and
50’ of 1/2” polypropylene rope. The hook and block clamp are mounted on an 8’ fiberglass
pole with a male splice on the bottom end to allow additional lengths of extensions to be
added as required.
CAT NO |
DESCRIPTION |
MAIN LINE RANGE MAXIMUM |
MAIN LINE RANGE MINIMUM |
MAXIMUM CABLE SIZE |
MAXIMUM FAULT CURRENT RATING |
LBS |
13761 |
GROUND CLAMP MOUNTED ON 8’ FIBERGLASS POLE WITH MALE SPLICE ON BOTTOM END |
3” DIA BUS OR CABLE |
6 STR 18 DIA |
4/0 |
54KA@ 15 CYCLES 39KA@ 30 CYCLES |
7.2 |
13762 |
GROUND CLAMP MOUNTED ON 8’ FIBERGLASS POLE WITH MALE SPLICE ON BOTTOM END |
6.625 DIA BUS |
1/0 STR .398 DIA |
4/0 |
54KA@ 15 CYCLES 39KA@ 30 CYCLES |
8.5 |
13763 |
GROUND LIFTING TOOL COMPLETE WITH “C” HOOK, HANDLINE BLOCK AND CLAMP, 50’ OF 1/2” POLYPROPYLENE ROPE INSTALLED ON A 8’ FIBERGLASS POLE WITH MALE SPLICE AT BOTTOM END |
8.0 |
||||
NOTE: EXTENSION AND BASE SECTIONS CAN BE ADDED FOR ADDITIONAL LENGTHS, SEE PAGE 107 |